SYNCHROTACT®Synchronizing and Paralleling devices and systems Data sheet
Date: Sept 24, 2024 Views: 894
SYNCHROTACT® MSP (Modular Synchronizing Panel) is a modular synchronizing system to synchronize generators and to parallel lines, built into a cubicle.
The measuring and metering feature, which is available in addition to the synchronizing system uses space conditions and already available signals in an optimum way.
The SYNCHROTACT® MSP includes:
SYNCHROTACT 5 Synchronizing system
• Automatic single or dual channel synchronizing system
• Manual synchronizing by means of a synchrocheck
• Local control panel
Electrical measuring and metering system
• Measuring system using transducers
• Metering system using power and energy meters
The system uses the proven and reliable SYNCHROTACT® 5 - components. Basically the synchronizing part includes an automatic and a redundant synchronizing feature (automatic or manual).
The modular concept allows to adapt the synchronizing system individually.
The following options are available:
1. Safety: single or dual channel solutions
2. Availability: redundant manual synchronizing or redundant automatic synchronizing or both
3. Number of circuit breakers to be synchronized: 1 to 4 CB's, one or more of them may be generator breakers
4. Power supply: in case of a redundant synchronizing, the power supply on the cubicle entrance can be redundant too.
5. Control: The control of the synchronizing is possible from remote in any case. An alternative local control is available as an option.
6. Adaptation of the measuring voltages: especially with synchronizing of several circuit breakers it may occur that the two secondary voltages have different amplitudes and phase angles with closed circuit breaker.
Synchronizing concept
Regarding availability, different solutions are possible:
Automatic synchronizing (sketch shows dual channel version) including separate synchrocheck
for redundant manual synchronizing (with its own hardware and power supply)
Automatic synchronizing (sketch shows dual channel version) using parameter set 7 as synchrocheck for manual synchronization.
Redundant, automatic dual channel synchronizing with the additional possibility of a manual synchronization (using parameter set 7)
The PC software SynView which is included with the delivery allows commissioning to be carried out quickly and simply.
The dead bus function, i.e., connection of voltage-free lines is possible in any case. Each individual situation can be included or excluded individually by parameter setting.
The measuring and metering part is available as an option. 3-phase voltage and current signals of a measuring point (e.g. gnerator, UAT, high voltage side) are used for measuring and
metering.
The values calculated from these signals can be locally displayed or are available as output signals.
Up to seven programmable
transducers with a three phase
current and voltage input each,
as well as four analog outputs to
display P, Q, S, U, I, f, pf
Up to four multifunctional power
meters with a three phase
current and voltage input each,
as well as four analog outputs to
display P, Q, S, U, I, f, pf;
accuracy class 0.5
Up to two energy meters with a
three phase current and voltage
input each; display of P, Q, S;
accuracy class 0.2, 0.5 and 1.0;
certified for clearing purposes
Related product recommendations:
CI810B 3BSE020520R1
CI853-1 3BSE018125R1
CI854A-EA 3BSE030221R2
CI854AK01 3BSE030220R1
CI854K01 3BSE025961R1
CI855K01 3BSE018106R1
CI855-1 3BSE018134R1
CI857K01 3BSE018144R1
CI858-1 3BSE018137R1
CI858K01 3BSE018135R1
CI867K01 3BSE043660R1
CI868K01-eA 3BSE048845R2
SYN6302-0202
SYN5202-5287
SYN5202-5277
SYN5202-5281
SYN5202-5271
SYN5202-4287
SYN5202-4281
SYN5202-4277
SYN5202-4271
SYN5202-3287
SYN5202-3281
more......